Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4355 Fox Run Trl

Approved

Filed Mar 22, 2025 by Taylor Vance, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Mar 22, 2025
Assembly type
RP
Serial number
B760204
Size
1
Test gauge serial
G-3855
Gauge calibration date
Jan 2, 2025
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-49-01035
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4355 Fox Run Trl
Owner: Avery Ramirez
Parcel 107-49-01035