← Backflow review queue
Backflow assembly test · 4303 Sycamore Way
ApprovedFiled Jun 26, 2024 by Taylor Vance, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 26, 2024
- Assembly type
- RP
- Serial number
- A878433
- Size
- 3/4
- Test gauge serial
- G-3284
- Gauge calibration date
- Dec 20, 2023
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-67-01183
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4303 Sycamore Way
Owner: Parker Wexler
Parcel 107-67-01183