Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6753 Sycamore Way

Approved

Filed Aug 21, 2024 by Reese Whitcomb, Heritage Backflow Testing · filed from phone

Report

Date of service
Aug 21, 2024
Assembly type
RP
Serial number
Z621289
Size
1
Test gauge serial
G-5461
Gauge calibration date
Dec 4, 2023
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-84-01020
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.