Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8879 Orchard Dr

Approved

Filed Oct 4, 2025 by Reese Nguyen, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Oct 4, 2025
Assembly type
RP
Serial number
K478423
Size
1
Test gauge serial
G-2175
Gauge calibration date
Aug 23, 2025
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-11-01135
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

8879 Orchard Dr
Owner: Casey Brandt
Parcel 107-11-01135