← Backflow review queue
Backflow assembly test · Maple Leaf Diner
ApprovedFiled Apr 30, 2026 by Reese Whitcomb, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Apr 30, 2026
- Assembly type
- RP
- Serial number
- Z430265
- Size
- 1 1/2
- Test gauge serial
- G-6200
- Gauge calibration date
- Mar 17, 2026
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 3.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-54-01010
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1601 Meadow Lark Trl
Owner: Kessler Holdings LLC
Parcel 107-54-01010