Backflow assembly test · 4707 Old Church Trl
ApprovedFiled Mar 3, 2025 by Reese Whitcomb, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Mar 3, 2025
- Assembly type
- RP
- Serial number
- K347342
- Size
- 3/4
- Test gauge serial
- G-8057
- Gauge calibration date
- Nov 17, 2024
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-24-01132
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.