← Backflow review queue
Backflow assembly test · Golden Pizza
ApprovedFiled Oct 5, 2025 by Hayden Pruitt, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 5, 2025
- Assembly type
- RP
- Serial number
- K237153
- Size
- 2
- Test gauge serial
- G-5322
- Gauge calibration date
- Mar 19, 2025
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-89-01209
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7216 Quarry Trl
Owner: Pruitt Holdings LLC
Parcel 107-89-01209