Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5460 Hickory Rd

Approved

Filed Feb 25, 2025 by Alex Pruitt, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Feb 25, 2025
Assembly type
PVB
Serial number
B555717
Size
1
Test gauge serial
G-5241
Gauge calibration date
Oct 23, 2024
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-53-01008
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

5460 Hickory Rd
Owner: Taylor Stroud
Parcel 107-53-01008