Backflow assembly test · 2209 Orchard Rd
ApprovedFiled Nov 29, 2025 by Reese Nguyen, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 29, 2025
- Assembly type
- RP
- Serial number
- K712305
- Size
- 3/4
- Test gauge serial
- G-5819
- Gauge calibration date
- Dec 13, 2024
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 3.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-79-01077
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.