Backflow assembly test · Station Pizza
ApprovedFiled Nov 11, 2024 by Reese Whitcomb, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Nov 11, 2024
- Assembly type
- RP
- Serial number
- W276438
- Size
- 1
- Test gauge serial
- G-3566
- Gauge calibration date
- Jul 8, 2023
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-25-01320
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.