Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 3696 Spring Branch Rd

Approved

Filed Dec 3, 2025 by Taylor Vance, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Dec 3, 2025
Assembly type
DC
Serial number
W331466
Size
1
Test gauge serial
G-6311
Gauge calibration date
Aug 15, 2025
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-26-01288
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3696 Spring Branch Rd
Owner: Quinn Pruitt
Parcel 107-26-01288