Backflow assembly test · 7268 Sycamore Ct

Approved

Filed Oct 31, 2026 by Reese Whitcomb, Heritage Backflow Testing · filed from phone

Report

Date of service
Oct 31, 2026
Assembly type
RP
Serial number
Z167044
Size
3/4
Test gauge serial
G-1272
Gauge calibration date
Mar 15, 2026
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-63-01145
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.