Pitkin County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Market

Approved

Filed Jan 3, 2025 by Alex Benton, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Jan 3, 2025
Assembly type
RP
Serial number
K648310
Size
1
Test gauge serial
G-5406
Gauge calibration date
Jan 3, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 097-98-01085
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4939 Orchard Ln
Owner: Wexler Holdings LLC
Parcel 097-98-01085