Backflow assembly test · Main Street Self Storage

Approved

Filed Sep 10, 2026 by Alex Benton, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Sep 10, 2026
Assembly type
DC
Serial number
K796519
Size
1 1/2
Test gauge serial
G-3385
Gauge calibration date
Sep 5, 2025
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
3.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 097-86-01027
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.