Pitkin County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6280 Meadow Lark Dr

Approved

Filed Dec 29, 2025 by Alex Benton, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Dec 29, 2025
Assembly type
RP
Serial number
K898060
Size
3/4
Test gauge serial
G-3640
Gauge calibration date
Aug 26, 2025
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 097-40-01300
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6280 Meadow Lark Dr
Owner: Taylor Vance
Parcel 097-40-01300