Backflow assembly test · 5238 Stone Gate Dr
ApprovedFiled Jul 26, 2025 by Jordan Ellery, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 26, 2025
- Assembly type
- DC
- Serial number
- W583018
- Size
- 1
- Test gauge serial
- G-4467
- Gauge calibration date
- Apr 27, 2025
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-92-01010
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.