Backflow assembly test · 5321 Laurel Dr
ApprovedFiled Oct 31, 2025 by Avery Nguyen, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 31, 2025
- Assembly type
- RP
- Serial number
- K171185
- Size
- 3/4
- Test gauge serial
- G-2367
- Gauge calibration date
- Feb 18, 2025
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-18-01209
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.