← Backflow review queue
Backflow assembly test · 7343 Meadow Lark Rd
ApprovedFiled Sep 15, 2025 by Avery Nguyen, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 15, 2025
- Assembly type
- RP
- Serial number
- W996251
- Size
- 3/4
- Test gauge serial
- G-1999
- Gauge calibration date
- Jul 28, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-99-01051
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7343 Meadow Lark Rd
Owner: Emerson Marsh
Parcel 097-99-01051