← Backflow review queue
Backflow assembly test · Maple Leaf Bakery
Needs reviewFiled Nov 18, 2026 by Jamie Hollins, Clearwater Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 18, 2026
- Assembly type
- RP
- Serial number
- W641017
- Size
- 4
- Test gauge serial
- G-6474
- Gauge calibration date
- Jul 26, 2026
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-61-01109
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
5119 Hickory Way
Owner: Danner Holdings LLC
Parcel 091-61-01109