← Backflow review queue
Backflow assembly test · 2803 Cedar Hollow Trl
ApprovedFiled Jul 15, 2025 by Cameron Benton, Lakeside Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 15, 2025
- Assembly type
- RP
- Serial number
- Z731711
- Size
- 1
- Test gauge serial
- G-5455
- Gauge calibration date
- Mar 12, 2025
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-72-01257
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2803 Cedar Hollow Trl
Owner: Parker Wexler
Parcel 091-72-01257