Ouray County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2803 Cedar Hollow Trl

Approved

Filed Jul 9, 2024 by Jamie Hollins, Clearwater Backflow Testing · filed from phone

Report

Date of service
Jul 9, 2024
Assembly type
RP
Serial number
Z731711
Size
1
Test gauge serial
G-4742
Gauge calibration date
Feb 18, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-72-01257
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2803 Cedar Hollow Trl
Owner: Parker Wexler
Parcel 091-72-01257