Backflow assembly test · 6412 Mill Creek Ct
ApprovedFiled Jun 1, 2025 by Cameron Benton, Lakeside Backflow Testing · filed from phone
Report
- Date of service
- Jun 1, 2025
- Assembly type
- RP
- Serial number
- K972372
- Size
- 3/4
- Test gauge serial
- G-6835
- Gauge calibration date
- Sep 5, 2024
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-88-01008
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.