Backflow assembly test · 3098 Old Church Ct

Approved

Filed May 10, 2026 by Cameron Benton, Lakeside Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
May 10, 2026
Assembly type
RP
Serial number
Z640236
Size
1
Test gauge serial
G-2041
Gauge calibration date
Oct 27, 2025
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-42-01113
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.