Backflow assembly test · 939 Pine Knoll Way
ApprovedFiled Sep 29, 2025 by Jamie Hollins, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Sep 29, 2025
- Assembly type
- RP
- Serial number
- Z648538
- Size
- 1
- Test gauge serial
- G-4477
- Gauge calibration date
- May 29, 2025
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-57-01094
- Readings in range, no flags
- Result: passing. Next due date resets when approved.