← Backflow review queue
Backflow assembly test · 939 Pine Knoll Way
ApprovedFiled Aug 31, 2024 by Jamie Hollins, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Aug 31, 2024
- Assembly type
- RP
- Serial number
- Z648538
- Size
- 1
- Test gauge serial
- G-9482
- Gauge calibration date
- Aug 11, 2023
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-57-01094
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
939 Pine Knoll Way
Owner: Avery Whitcomb
Parcel 091-57-01094