Ouray County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5346 Stone Gate Ct

Approved

Filed Nov 9, 2025 by Sam Calloway, Lakeside Backflow Testing · filed from phone

Report

Date of service
Nov 9, 2025
Assembly type
RP
Serial number
K679652
Size
3/4
Test gauge serial
G-4160
Gauge calibration date
Apr 10, 2025
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
2.4 psid
Relief valve opened at
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-57-01244
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5346 Stone Gate Ct
Owner: Rowan Lindqvist
Parcel 091-57-01244