Backflow assembly test · 3704 Fox Run Trl
ApprovedFiled Dec 13, 2025 by Jamie Hollins, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Dec 13, 2025
- Assembly type
- RP
- Serial number
- A136669
- Size
- 3/4
- Test gauge serial
- G-2657
- Gauge calibration date
- May 8, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-75-01258
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.