Backflow assembly test · 5340 Mill Creek Ln
Needs reviewFiled Nov 19, 2026 by Taylor Calloway, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 19, 2026
- Assembly type
- DC
- Serial number
- W923039
- Size
- 1
- Test gauge serial
- G-4578
- Gauge calibration date
- Nov 6, 2025
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 081-96-01177
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
5340 Mill Creek Ln
Owner: Avery Harlow
Parcel 081-96-01177