Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Taqueria

Approved

Filed Oct 14, 2025 by Taylor Calloway, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Oct 14, 2025
Assembly type
RP
Serial number
A692580
Size
1
Test gauge serial
G-7301
Gauge calibration date
Feb 13, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-19-01268
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

430 Meadow Lark Ct
Owner: Okafor Holdings LLC
Parcel 081-19-01268