Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2233 Sycamore Rd

Approved

Filed Mar 13, 2026 by Taylor Calloway, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Mar 13, 2026
Assembly type
RP
Serial number
K613958
Size
3/4
Test gauge serial
G-3555
Gauge calibration date
Jul 25, 2025
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-90-01142
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2233 Sycamore Rd
Owner: Cameron Ashby
Parcel 081-90-01142