Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2233 Sycamore Rd

Approved

Filed Feb 16, 2025 by Logan Lindqvist, Ridge Backflow Testing · filed from phone

Report

Date of service
Feb 16, 2025
Assembly type
RP
Serial number
K613958
Size
3/4
Test gauge serial
G-7962
Gauge calibration date
Nov 12, 2024
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-90-01142
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2233 Sycamore Rd
Owner: Cameron Ashby
Parcel 081-90-01142