Backflow assembly test · 5090 Spring Branch Ct
ApprovedFiled Nov 9, 2025 by Casey Nguyen, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 9, 2025
- Assembly type
- DC
- Serial number
- Z643717
- Size
- 1
- Test gauge serial
- G-1626
- Gauge calibration date
- Aug 30, 2025
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 081-65-01075
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.