Backflow assembly test · 8469 Turkey Hill Trl
ApprovedFiled Oct 27, 2026 by Blake Ashby, Heritage Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 27, 2026
- Assembly type
- RP
- Serial number
- W968942
- Size
- 3/4
- Test gauge serial
- G-1270
- Gauge calibration date
- Sep 28, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 1.6 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 081-95-01292
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8469 Turkey Hill Trl
Owner: Quinn Kessler
Parcel 081-95-01292