← Backflow review queue
Backflow assembly test · 7193 Orchard Trl
ApprovedFiled Apr 20, 2025 by Emerson Lindqvist, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 20, 2025
- Assembly type
- RP
- Serial number
- W305565
- Size
- 3/4
- Test gauge serial
- G-9906
- Gauge calibration date
- Oct 22, 2024
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 081-14-01192
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7193 Orchard Trl
Owner: Jamie Harlow
Parcel 081-14-01192