← Backflow review queue
Backflow assembly test · 4360 Pine Knoll Trl
ApprovedFiled Jun 17, 2024 by Taylor Calloway, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 17, 2024
- Assembly type
- PVB
- Serial number
- K101613
- Size
- 1
- Test gauge serial
- G-1153
- Gauge calibration date
- Nov 27, 2023
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 081-67-01248
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4360 Pine Knoll Trl
Owner: Parker Whitcomb
Parcel 081-67-01248