Backflow assembly test · 6709 Ridgeview Trl

Approved

Filed Dec 4, 2024 by Drew Nguyen, Ridge Backflow Testing · filed from phone

Report

Date of service
Dec 4, 2024
Assembly type
RP
Serial number
K848547
Size
3/4
Test gauge serial
G-5448
Gauge calibration date
Aug 22, 2024
Check valve 1
0.8 psid
Check valve 1 closed tight
No
Check valve 2
1.2 psid
Relief valve opened at
2.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-16-01305
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6709 Ridgeview Trl
Owner: Shawn Okafor
Parcel 081-16-01305