Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 3178 Hickory Trl

Approved

Filed Sep 10, 2025 by Drew Nguyen, Ridge Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Sep 10, 2025
Assembly type
PVB
Serial number
B839447
Size
1
Test gauge serial
G-6067
Gauge calibration date
Jun 27, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-99-01260
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

3178 Hickory Trl
Owner: Casey Okafor
Parcel 081-99-01260