Mesa County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 3742 Quarry Trl

Approved

Filed May 24, 2026 by Jordan Harlow, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
May 24, 2026
Assembly type
DC
Serial number
A992605
Size
3/4
Test gauge serial
G-9942
Gauge calibration date
Nov 4, 2025
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 077-12-01001
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3742 Quarry Trl
Owner: Avery Ellery
Parcel 077-12-01001