Mesa County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4321 Laurel Ct

Approved

Filed Mar 2, 2025 by Jordan Harlow, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Mar 2, 2025
Assembly type
RP
Serial number
Z712865
Size
1
Test gauge serial
G-4473
Gauge calibration date
Sep 12, 2024
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 077-26-01115
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4321 Laurel Ct
Owner: Shawn Harlow
Parcel 077-26-01115