Backflow assembly test · 6236 Orchard Rd
ApprovedFiled Oct 17, 2025 by Jamie Marsh, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 17, 2025
- Assembly type
- DC
- Serial number
- W943560
- Size
- 3/4
- Test gauge serial
- G-1421
- Gauge calibration date
- Aug 8, 2025
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-25-01131
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6236 Orchard Rd
Owner: Drew Wexler
Parcel 077-25-01131