Mesa County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7774 Meadow Lark Ln

Filed Nov 18, 2026 by Jordan Harlow, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Nov 18, 2026
Assembly type
RP
Serial number
W438495
Size
3/4
Test gauge serial
G-6269
Gauge calibration date
Feb 16, 2026
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
1.8 psid
Relief valve opened at
4.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 077-75-01305
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Property

7774 Meadow Lark Ln
Owner: Rowan Danner
Parcel 077-75-01305