Backflow assembly test · Crossroads Elementary School

Approved

Filed Nov 5, 2026 by Jordan Harlow, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Nov 5, 2026
Assembly type
RP
Serial number
A278769
Size
1 1/2
Test gauge serial
G-6093
Gauge calibration date
Jan 12, 2026
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 077-35-01133
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8044 Mill Creek Way
Owner: Vance Holdings LLC
Parcel 077-35-01133