Mesa County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 9484 Laurel Rd

Approved

Filed Nov 21, 2025 by Jamie Marsh, Lakeside Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Nov 21, 2025
Assembly type
RP
Serial number
Z299714
Size
3/4
Test gauge serial
G-7320
Gauge calibration date
Apr 3, 2025
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 077-19-01282
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9484 Laurel Rd
Owner: Avery Wexler
Parcel 077-19-01282