Backflow assembly test · 2764 Laurel Way

Approved

Filed Nov 3, 2026 by Morgan Calloway, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Nov 3, 2026
Assembly type
PVB
Serial number
K221816
Size
1
Test gauge serial
G-2776
Gauge calibration date
May 20, 2026
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 077-50-01218
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2764 Laurel Way
Owner: Emerson Vance
Parcel 077-50-01218