Backflow assembly test · 1390 Turkey Hill Ln
ApprovedFiled Dec 20, 2023 by Jamie Marsh, Lakeside Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Dec 20, 2023
- Assembly type
- PVB
- Serial number
- W623015
- Size
- 1
- Test gauge serial
- G-3098
- Gauge calibration date
- Aug 31, 2023
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-68-01321
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.