Backflow assembly test · 2717 Pine Knoll Trl
ApprovedFiled Oct 5, 2026 by Logan Whitcomb, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 5, 2026
- Assembly type
- RP
- Serial number
- B974717
- Size
- 3/4
- Test gauge serial
- G-9966
- Gauge calibration date
- Aug 25, 2026
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-75-01201
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.