Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7571 Ridgeview Way

Approved

Filed Oct 29, 2025 by Hayden Ramirez, Patriot Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Oct 29, 2025
Assembly type
DC
Serial number
B689760
Size
1
Test gauge serial
G-1782
Gauge calibration date
Sep 26, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-88-01041
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7571 Ridgeview Way
Owner: Alex Danner
Parcel 069-88-01041