Backflow assembly test · 2411 Orchard Ln
ApprovedFiled May 7, 2026 by Hayden Ramirez, Patriot Backflow Testing · filed from phone
Report
- Date of service
- May 7, 2026
- Assembly type
- RP
- Serial number
- W710145
- Size
- 1
- Test gauge serial
- G-7940
- Gauge calibration date
- Aug 8, 2025
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-87-01031
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.