Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 234 Laurel Way

Approved

Filed Oct 23, 2024 by Taylor Pruitt, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Oct 23, 2024
Assembly type
RP
Serial number
B703395
Size
3/4
Test gauge serial
G-2988
Gauge calibration date
Jun 28, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-56-01303
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

234 Laurel Way
Owner: Avery Ramirez
Parcel 069-56-01303