Backflow assembly test · Crossroads Taqueria
ApprovedFiled Apr 28, 2026 by Blake Marsh, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Apr 28, 2026
- Assembly type
- RP
- Serial number
- A972205
- Size
- 1 1/2
- Test gauge serial
- G-5516
- Gauge calibration date
- Feb 23, 2026
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-55-01172
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.